RTD Cables are used as an extension wire to transmit Signal from RTD Sensor to Control Unit. They are available in 2,3,4,6, cores as per the requirement of RTD SENSOR design for Simplex & Duplex Construction.
The most popular design is of PTFE Insulation & outer jacket of PTFE, GLASS FIBER & SILICONE RUBBER as per requirement. Metal over braid of SS & SPC, if required.
ELTEC RTD wires conforms to US Military MIL – W – 16878 and Indian defense specifications JSS 51034.92. As per these standards, PTFE Insulated RTD wires are classified in three main working voltage grades.
GRADE |
SPARK TESTING |
DIE ELECTRIC TESTING |
ET (250 V) |
2500 V AC |
1500 V AC |
E (600 V) |
3400 V AC |
2000 V AC |
EE (1000 V) |
5000 V AC |
3000 V AC |
- RTD Sensors & Extension Wires
- RTD Autoclave
- Medical Instruments & Scientific Equipments
- Sensors, Load Cells & Pressure Transducers
- Electronics & Communication Equipment
- Process Instrumentation
- Continuous use up to 260 °C
- Intermittent use up to 300 °C
- High dielectric values
- Non flammable, non toxic
- High strain & abrasion resistance
- Immune to agene, fungus
- Conductor - Silver Plated Copper wires sizes from 28 AWG to 20 AWG as per MIL – W - 16878 & JSS 51034, Refer Table for most popular & standard wire sizes
- Core Insulation - Fused PTFE Tape , Fiber Glass, Silicone Rubber Extruded, Refer Ordering Code
- No. of Pair or Triad - 1, 2, 3 or more
- Construction - Twisted
- Outer Sheath - Fused PTFE Tape , Fiber Glass Insulated, Silicone Rubber Extruded, Refer Ordering Code
- Screening - Silver Plated Copper wire Braid or SS Over Metal Braid
- Color Code - Confirms to EN 60751
• Other types of Insulation & Jacket such as PVC, FEP, PFA is available on request.
• Screening of SS or Silver Plated Copper wire with Outside Jacket of PTFE
• Few Popular Conductor Sizes confirming to MIL – W – 16878 & JSS 51034 are as per the table
- Conductor: Silver Plated Copper , Nickel Plated Copper, Tin Plated Copper
- Insulation: PVC, FEP, PFA, SILICONE RUBBER, PTFE, FIBER GLASS, CERAMIC FIBER
- Jacket: PVC, PTFE, FEP, PFA, SILICONE RUBBER, FIBER GLASS, CERAMIC FIBER
- Shielding: SS Metal Braid, Silver Plated Copper Wire, Alu. Mylar with Drain Wire
RTD WIRE ORDERING CODE